How to troubleshoot a solenoid valve that does not operate after energisation?

Solenoid valve · 18 November 2026

Check in sequence: ① whether the coil is energised (measure voltage with a multimeter); ② whether the coil is burnt out (measure resistance; open circuit means damaged); ③ whether the spool is stuck (media impurities or scaling); ④ whether pressure/pressure differential meets the pilot valve opening requirement; ⑤ whether the installation direction is correct. Eliminate items one by one in this order.

A pilot valve that does not operate at low pressure is often due to insufficient opening pressure differential; a zero-pressure opening type (e.g. ASCO 327) can be selected instead.