IsoPAQ-612 loop-powered isolator
The input loop-powered isolator IsoPAQ-612 provides electrical isolation for 0(4)…20 mA standard signals and transmits the measurement signal to the output with high accuracy.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
The input loop-powered isolator IsoPAQ-612 provides electrical isolation for 0(4)…20 mA standard signals and transmits the measurement signal to the output with high accuracy.
The device prevents interference voltages from entering and effectively suppresses parasitic noise. Its extremely low voltage drop of 2.3 V and high accuracy make the IsoPAQ-612 the first choice in system design.
The intelligent design avoids the use of highly integrated components, resulting in an extremely long service life and high reliability without distorting the measurement signal.
The IsoPAQ-612 requires no additional power supply; the auxiliary power is drawn from the input signal without causing signal distortion. This not only saves installation costs but also increases reliability.
| Parameter Name | Technical Specifications |
|---|---|
| Technical specifications | |
| Input Signal | 0(4)-20 mA |
| Start-up current | < 200 mA |
| Voltage drop | Ca. 2.3 V at 20 mA |
| Overload | ≤ 50 mA, 30 V |
| Output Signal | 0(4)-20 mA |
| Load | 600 Ω |
| Response time T99 | 5 ms |
| Residual ripple | < 10 mV rms |
| Transmission error | < 0.1 % full scale |
| Load error | < 0.05 % of measured value / 100 Ω load |
| Temperature coefficient | < 100 ppm/K |
| Test voltage | 3 kV AC, 50 Hz, 1 min. all circuits against one another |
| Operating voltage (basic insulation) | 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 |
| Protection against electric shock | Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. |
| Ambient Temperature | Operation – 25 to + 70 °C (– 13 to + 158 °F) Transport and Storage – 40 to + 85 °C (– 40 to + 185 °F) |
| Electromagnetic compatibility | EN 61326-1 |
| Structure type | 62 x 96.5 x 107 mm, protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715 |
| Weight | Approx. 70 g |
- The input loop-powered isolator IsoPAQ-612 provides electrical isolation for 0(4)…20 mA standard signals and transmits the measurement signal to the output with high accuracy.
- The device prevents interference voltages from entering and effectively suppresses parasitic noise. Its extremely low voltage drop of 2.3 V and high accuracy make the IsoPAQ-612 the first choice in system design.
- The intelligent design avoids the use of highly integrated components, resulting in an extremely long service life and high reliability without distorting the measurement signal.
Process loop signal isolation
Interfaces two-wire transmitters with the control system in DCS/PLC analogue loops, eliminating measurement errors caused by ground potential differences and earth loops.
Hazardous area signal conditioning
In refining and petrochemical units, 4–20 mA signals are isolated and distributed to the control system and safety interlock loops, ensuring a reliable signal chain.
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232
- Email inquiry web@qishan-sh.com