SC2043 Analogue Input Isolator (single-channel, one-in two-out)

Product Model SC2043

Product Brand

Product Category Industrial safety and signal conditioning modules / signal isolators, industrial safety and signal conditioning modules

Application Industry Petrochemical, process automation

Economical analogue input isolator: 4-20mA input isolated and converted to 4-20mA output, single-channel, one-in two-out, three-terminal isolation, requires independent power supply.

Inquire Now
  • Original Factory Genuine, Tenfold Compensation for Counterfeits
  • Full Machine Warranty, Lifetime Maintenance
  • In Stock, Shipped on the Same Day

Analogue input isolator (economy type), which isolates the input current and converts it to current or voltage signal output. This product requires an independent power supply, with three-port isolation between input, output and power supply, DIN-rail mounting, pluggable grey terminals, and green power indicator.

SC2043 Analogue Input Isolator (Single Channel, One In Two Out) Technical Specifications
Parameter Name Technical Specifications
Power supply and power consumption
Power Supply 20V DC ~ 32V DC
Power consumption ≤1.8W (24V, one in two out, full load output)
Input characteristics
Input Signal 4~20mA
Input Impedance DC current: 60Ω, DC voltage: ≥1MΩ
Distribution voltage Open-circuit voltage ≤25V, output voltage ≥16V at 20mA
Output and load
Output Signal 4~20mA
Permissible load Active current: 0/4~20mA RL ≤ 450Ω
Wiring Instructions 24V supply, one in two out, current output
Accuracy and response
Conversion accuracy 0.1%F.S (25°C±2°C)
Temperature drift 40ppm/°C
Response time ≤2ms
Isolation and Environment
Electromagnetic compatibility IEC 61326-3-1
Dielectric strength ≥1500V AC (between input/output/power supply)
Insulation resistance ≥100MΩ (between input/output/power supply)
Operating Temperature -20°C~+60°C
Storage Temperature -40°C~+80°C
Output Status
Output Status Unless otherwise specified by the user, regardless of the fault condition of the input signal, the output follows the input signal variation over the full scale range (except for wire break, where the output is 0V/mA), but never exceeds 110% of the upper output range limit
  • 4-20mA current input, isolated conversion to 4-20mA current output
  • Three-terminal isolation of input, output and power supply, dielectric strength ≥1500V AC
  • Conversion accuracy 0.1%F.S, temperature drift 40ppm/°C, response time ≤2ms
  • 12.8mm ultra-slim DIN rail mounting, pluggable terminals
  • EMC compliant with IEC 61326-3-1

One input split into two outputs

One 4-20mA signal feeds both DCS and local display/recorder simultaneously; the two outputs are independent and do not affect each other

Need selection advice or bulk quotation?

Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.

Please fill in the name

Please fill in a valid contact phone number (7-20 digits)

Please enter a valid email address

Inquire about the product

SC2043 · SC2043 Analogue Input Isolator (Single Channel, One In Two Out)

Please enter the requirement description (at least 10 characters)

Online customer service
Online customer service Scan or click to contact directly
Contacts
Miss Chen(Safety barriers, isolators, surge protectors)
陈小姐 个人微信二维码

Scan WeChat QR code to add personal WeChat

QQ:2501529964

Phone:17717626508

Email:chenjing@qishan-sh.com

Miss Lu(Field Instruments, Valve Accessories, Terminal Blocks)
卢小姐 个人微信二维码

Scan WeChat QR code to add personal WeChat

QQ:1695457483

Phone:13636420802

Email:lhm@qishan-sh.com

Mr. Ye(Technical Support, After-Sales Service)

QQ:97010638

Phone:15800474322

Email:web@qishan-sh.com

Online Message

Please fill in the name

Please fill in a valid contact phone number (7-20 digits)

Please enter a valid email address

Please enter the requirement description (at least 10 characters)