In most cases yes, but the loop parameters and wiring must be re-verified. Isolators require a working power supply such as 24 V DC, whereas Zener barriers are usually passive; isolators have input-output isolation and low earthing requirements. When replacing, confirm that the power supply, signal type, number of channels, explosion protection marking and field instrument parameters match.
After replacement, loop testing should be carried out and the explosion protection register updated to ensure the modified loop still meets intrinsically safe requirements.