Common causes: excessive voltage drop in the two-wire circuit causing undervoltage of the transmitter, load exceeding the drive capability of the safety barrier, excessive terminal contact resistance, interference introduced by poor earthing, or range/polarity mismatch.
Use a multimeter to measure the circuit voltage and current stage by stage, verify the total load and supply margin, and check shielding and earthing. For isolation barriers, also confirm that the input and output mode settings are correct.