When the hazardous-area side of a Zener barrier is short-circuited, the current-limiting resistor and fuse limit and cut off the energy so that the short-circuit current is insufficient to ignite gas (the expected behaviour of the intrinsically safe design); the fuse may blow. Isolated barriers usually have short-circuit protection and can recover after the fault is cleared.
After a short circuit occurs, identify the cause before restoring operation; after a Zener barrier fuse blows, it must be replaced with a certified fuse of the same rating and must not be bypassed.