Zone classification is based onthe frequency and duration of the presence of explosive atmospheres, not on a subjective judgement of hazard level. The classification method is clearly specified in GB 50058 and IEC 60079-10-1.

| Zone | Frequency of occurrence | Acceptable intrinsic safety rating | Equipment protection level |
|---|---|---|---|
| Zone 0 | Continuous / long-term / short-term frequent | Ex ia | Ga |
| Zone 1 | Occasional during normal operation | Ex ia, Ex ib | Ga, Gb |
| Zone 2 | Short-term only under abnormal conditions | Ex ia, Ex ib, Ex ic | Ga, Gb, Gc |
Responsibility boundary:Zone classification shall be issued by a qualified design institute, and equipment selection must be based on that classification drawing. Judging zones on site by "looks about right" is the most common source of compliance risk in explosion protection management. Where the equipment list and the zone classification drawing are inconsistent, the classification drawing shall prevail and changes shall be traced.