Isolation Distances and Identification for Intrinsically Safe and Non-Intrinsically Safe Circuits

Intrinsic Safety Basics · 23 November 2026

Once intrinsically safe circuits are mixed with non-intrinsically safe circuits, unrestricted energy may be introduced through insulation damage, inductive coupling, or miswiring, and the entire intrinsically safe property is lost. Therefore, the standards impose explicit requirements for "separation".

Three mandatory rules

  • Must not share cables: Intrinsically safe circuits and non-intrinsically safe circuits must not be laid in the same cable, nor may they share the spare cores of the same multicore cable;
  • Separate routing: They shall be laid separately in cable trays and trunking, with a spacing typically not less than 50 mm; where conditions are restricted, metal barriers or metal conduit must be installed;
  • Colour and identification: Intrinsically safe circuits should use a blue outer sheath, or "Intrinsically Safe Circuit" labels shall be fitted at both ends and at regular intervals, and terminal blocks shall also be distinctively marked.
Case Permitted Conditions
Different intrinsically safe circuits sharing a cable Permitted under conditions The cumulative effect of Co/Lo of each circuit must be verified, and the manufacturer and standards must permit it
Intrinsically safe and non-intrinsically safe circuits sharing a cable not permitted —
Intrinsically safe and non-intrinsically safe circuits in the same cable tray Permitted under conditions Fit a barrier or metal conduit, spacing ≥50 mm
Intrinsically safe circuits in the same steel conduit not permitted Unless only intrinsically safe circuits are in the steel conduit

Common problems on modification sites:To save effort when adding points, the intrinsically safe signal wires are pushed into the spare cores of existing non-intrinsically safe cables. This connection looks fine on the drawings but constitutes a substantive violation and will be judged a hazard in every subsequent explosion protection inspection. Once found, the entire cable must be replaced; labelling alone is not sufficient.

← Back to Knowledge Sharing

Online customer service
Online customer service Scan or click to contact directly
Contacts
Miss Chen(Safety barriers, isolators, surge protectors)
Ms Chen Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:2501529964

Phone:17717626508

Email:chenjing@qishan-sh.com

Miss Lu(Field Instruments, Valve Accessories, Terminal Blocks)
Ms Lu Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:1695457483

Phone:13636420802

Email:lhm@qishan-sh.com

Mr. Ye(Technical Support, After-Sales Service)

QQ:97010638

Phone:15800474322

Email:web@qishan-sh.com

Online Message

Please fill in the name

Please fill in a valid contact phone number (7-20 digits)

Please enter a valid email address

Please enter the requirement description (at least 10 characters)