Once intrinsically safe circuits are mixed with non-intrinsically safe circuits, unrestricted energy may be introduced through insulation damage, inductive coupling, or miswiring, and the entire intrinsically safe property is lost. Therefore, the standards impose explicit requirements for "separation".
Three mandatory rules
- Must not share cables: Intrinsically safe circuits and non-intrinsically safe circuits must not be laid in the same cable, nor may they share the spare cores of the same multicore cable;
- Separate routing: They shall be laid separately in cable trays and trunking, with a spacing typically not less than 50 mm; where conditions are restricted, metal barriers or metal conduit must be installed;
- Colour and identification: Intrinsically safe circuits should use a blue outer sheath, or "Intrinsically Safe Circuit" labels shall be fitted at both ends and at regular intervals, and terminal blocks shall also be distinctively marked.
| Case | Permitted | Conditions |
|---|---|---|
| Different intrinsically safe circuits sharing a cable | Permitted under conditions | The cumulative effect of Co/Lo of each circuit must be verified, and the manufacturer and standards must permit it |
| Intrinsically safe and non-intrinsically safe circuits sharing a cable | not permitted | — |
| Intrinsically safe and non-intrinsically safe circuits in the same cable tray | Permitted under conditions | Fit a barrier or metal conduit, spacing ≥50 mm |
| Intrinsically safe circuits in the same steel conduit | not permitted | Unless only intrinsically safe circuits are in the steel conduit |
Common problems on modification sites:To save effort when adding points, the intrinsically safe signal wires are pushed into the spare cores of existing non-intrinsically safe cables. This connection looks fine on the drawings but constitutes a substantive violation and will be judged a hazard in every subsequent explosion protection inspection. Once found, the entire cable must be replaced; labelling alone is not sufficient.