Because the energy level in the hazardous area is determined jointly by all three; if any one link exceeds the limit, the whole does not hold. This is similar to the "cask effect": the safety margin of the system depends on the weakest item.
| Assessment item | Inequality | Consequence of exceeding limit |
|---|---|---|
| Voltage | Uo ≤ Ui |
Overvoltage at the input stage of field equipment, insulation breakdown |
| Current | Io ≤ Ii |
Current-limiting element overheating, or overcurrent in the intrinsically safe side circuit |
| Power | Po ≤ Pi |
Energy exceeds the ignition threshold |
| Capacitance | Ci + Cc ≤ Co |
Increased stored energy, higher spark energy |
| Inductance | Li + Lc ≤ Lo |
Inductive overvoltage occurs on disconnection, causing arcing |
Why consider capacitance and inductance, not just voltage and current:Ignition energy comes not only from the continuous output of the power supply, but also from the instantaneous release of energy storage components. The longer the cable, the greater the distributed capacitance, and the more energy released at the moment of disconnection. This is also why long-distance intrinsically safe circuits are sometimes limited by capacitance rather than voltage.
Practical recommendations:Turn these five inequalities into a checklist and archive it together with the loop list. Every time an instrument is replaced, a cable is lengthened, or wiring is changed, recalculate on the form and sign it. This form is the most direct compliance evidence during explosion protection acceptance and safety inspections, far more effective than verbal explanations.