Simple apparatus has no nameplate parameter table, so values must be assigned by component type. The three common types are as follows.
| Device type | Ui / Ii / Pi | Ci / Li | Assessment method |
|---|---|---|---|
| Thermocouples | Based on the loop's operating voltage and current, usually far below the barrier limits | Can be ignored (on the order of a few pF) | Mainly assess cable length |
| RTD (Pt100) | As above | Negligible | Note the effect of lead resistance on measurement |
| Mechanical switch / pushbutton | As above | Negligible | Note contact rating and bounce |
| Junction box (empty) | — | Estimated from terminal blocks, generally very small | Must be re-assessed after adding components inside the box |
Strictly speaking, the "Ui" of simple apparatus should be taken as the maximum voltage it can withstand. Passive components such as thermocouples and switches have no rated voltage concept of their own; in engineering practice, the criterion is that "the barrier's Uo will not cause damage", while also confirming that their insulation can withstand that voltage.
Common pitfalls:If a temperature transmitter module (DIN-rail mounted) is also present between the thermocouple loop and the safety barrier, that module is no longer simple apparatus; it must hold an intrinsically safe certificate, and its Ci/Li must be included in the loop. Many sites treat "thermocouple + integrated transmitter" as simple apparatus, which is wrong.
Compensation cable:Compensation cables used with thermocouples also have distributed capacitance and inductance, and their materials differ from ordinary copper cables; parameters should be taken from the compensation cable datasheet. Replacing compensation cable with ordinary cable not only affects temperature measurement accuracy but also invalidates the basis for intrinsic safety calculations.