Yes. And it is a problem at two levels:Energy level(capacitance and inductance superposition) andSignal level(crosstalk and common-mode interference).
Energy level
For multiple pairs of intrinsically safe circuits in the same cable, distributed capacitance exists between the cores. When a fault occurs in one pair, energy may couple to another pair through the inter-core capacitance. Standards permit intrinsically safe circuits to share a cable, but only on the premise that verification is performed for the worst-case combination and that the coupled energy is confirmed to remain within limits.
Signal level
- Crosstalk: capacitive coupling between adjacent cores couples the signal of one circuit into another, manifesting as "when point A fluctuates, point B follows";
- Common-mode interference: when multiple circuits share a shield, interference currents on the shield couple into all circuits simultaneously.
Practical recommendations:Use one cable per analogue loop wherever possible; where cables must be shared, group signals of the same type together (mA with mA, discrete with discrete) and avoid running millivolt-level thermocouple signals in the same cable as 24 V discrete signals. The latter is the most common source of on-site interference problems.
Shield handling:When cables are shared, the shield is usually common and is earthed at one end on the safe-area side. If the source earth potentials of the various signals differ significantly, a common shield will instead introduce circulating currents; in this case, consider separate cables or isolated barriers.