Shielding and earthing for intrinsically safe circuits follow the basic principles of "single-point earthing, earthed on the safe-area side", the aim being to suppress interference without creating earth circulating currents.
| Item | Practice | Reason |
|---|---|---|
| Shield earthing point | Single-point earthing on the safe-area side | Avoids circulating currents caused by the potential difference between the two earth points |
| Shield on the hazardous-area side | Floating, with insulation treatment | Prevents multiple connections to the on-site earthing grid |
| Shield continuity | Connected through at intermediate junction boxes, not cut | Ensures effective shielding over the entire run |
| Armour layer | Treat as protective earthing, earth at both ends | The armour serves as mechanical protection and an earthing conductor, and is unrelated to intrinsic safety energy limitation |
Take care to distinguish the shield layer from the armour layer: The shield layer performs the interference-suppression function and is earthed at one end; the armour layer provides mechanical protection and a fault-current path, and is earthed at both ends per protective earthing requirements. The two must not be confused, nor should the armour be used as a shield.
A typical fault:The site reported 50 Hz interference on the signal, and inspection found that the shield layer was also earthed on the hazardous-area side. With both ends earthed, the earth potential difference produced a circulating current in the shield layer, which instead coupled interference into the signal line. After disconnecting the hazardous-area-side earth, the interference disappeared. When troubleshooting such problems, check the shield earthing point first — it is faster than replacing instruments.