IPAQ R460 Four-wire Signal Transmitter
Programmable four-wire (independent power supply) isolated transmitter, supporting Pt, Ni, KTY, thermocouple, potentiometer, resistance, and mV input, which can be configured via DIP switch or INOR-Set software.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
The IPAQ R460 is a programmable four-wire (independent power supply) transmitter that can convert Pt, Ni, KTY, thermocouple signals, as well as potentiometer, resistance, and mV signals into isolated standard signal outputs.
The IPAQ R460 can be configured via DIP switch or INOR-Set software. When using INOR-Set, configuration can be completed on a PC, and data can be recorded and archived; no additional power supply is required during PC configuration.
The debug (commissioning) function on the front panel, which can be opened, generates a reference signal at the output end, making it easy to test and adjust subsequent signal channels. Power can be supplied by terminal blocks or In-Rail-Bus connectors, and the front panel LED indicates the supply voltage and fault status.
| Parameter Name | Technical Specifications |
|---|---|
| Basic Parameters | |
| Product Type | Rack-mounting Type |
| Transmitter Type | Digital |
| Measurement Channels | Single Channel |
| Structural Design | 6.2 mm (0.244″) side-by-side housing, protection class IP20, mounted on a 35 mm top hat rail that complies with EN 60715. |
| Weight | Approx. 70 g |
| Input | |
| Input Signal | Resistance Thermometers, Thermocouples, mV, Resistance, and KTY |
| RTD Input | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni500, Ni1000 |
| Thermocouple Input | Types B, E, J, K, L, N, R, S, T, U, W5Re_W26Re, W3Re_W25Re |
| RTD Measurement Range | Pt 100, Pt 200, Pt 500, Pt 1000: -200… +850 °C Ni 100: -60… +250 °C Ni 200, Ni 500, Ni 1000: -50… 180 °C |
| Thermocouple Measurement Range | Type B: +250...+1820 °C, Type C (W5Re_W26Re): 0...+2315 °C, Type D (W3Re_W25Re): 0...+2315 °C, Type E: +270...+1000 °C, Type J: +210...+1200 °C, Type K: +200...+900 °C, Type L: +200...+900 °C, Type N: +270...+1300 °C, Type R: -50...+1768 °C, Type S: -50...+1768 °C, Type T: -270...+400 °C, Type U: +200...+600 °C |
| Sensor Wiring | 2-wire, 3-wire, 4-wire wiring |
| Output and Communication | |
| Output Signal | 0...20 mA, 4...20 mA, 0...10 mA, 2...10 mA, 0...5 V, 0...10 V, 1...5 V, 2...10 V |
| Configuration Mode | DIP switch or INOR-Set software |
| Power Supply and Isolation | |
| Electrical Isolation | 3 kV AC, 50 Hz, for 1 minute |
| Power Supply | 24 V DC voltage range 9.6...31.2 VDC, power consumption approx. 0.8 W |
| Accuracy and Environment | |
| Typical Accuracy | Maximum ±0.05 K or ±0.05% measurement range |
| Ambient Temperature | Operating temperature: -25...+70 °C (-13...+158 °F), Storage and transport temperature: -40...+85 °C (-40...+185 °F) |
| Certification and Compliance | |
| Electromagnetic Compatibility (EMC) | EN 61326-1 |
- Configurable via DIP switch or INOR-Set software
- Switchable operational (debugging) function for quick startup
- 3-port isolation: prevents ground issues and interference voltage from causing measurement errors
- Extremely narrow design: 6.2 mm parallel housing, top cap rail installation is simple and space-saving
- Optional In-Rail-Bus connector for quick installation and lower cost
- Safety isolation in accordance with EN 61140, protecting maintenance personnel and downstream equipment from abnormal high-voltage hazards
- Supports Pt, Ni, KTY, thermocouples, potentiometers, resistors, and mV inputs
Signal Conversion and Isolation
Converts potentiometers, resistors, mV, etc., to isolated standard signals, eliminating ground loop and interference intrusion.
Equipment Sets and Integration
Quickly powered via In-Rail-Bus connectors, suitable for bulk cabinet and equipment integration delivery.
On-site debugging and verification
The commissioning function generates reference signals at the output end, facilitating rapid verification of subsequent signal channels.
Documents not uploaded. Please fill in the information row by row in the 'Product Details Field' panel under 'File Name | Download Address | File Size'.
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232
- Email inquiry web@qishan-sh.com