Intrinsic safety grounding should use adedicated, low-impedance, reliablegrounding path; the Zener barrier grounding terminal is connected to the intrinsic safety grounding busbar and then connected to the grounding grid at a single point. The grounding resistance should meet the requirements of the standards and the product, and arbitrary common bonding with power grounds or lightning protection down conductors should be avoided.
After installation, measure earthing continuity and resistance and keep records; during operation, periodically check terminals for looseness and corrosion. Although isolating barriers do not rely on intrinsically safe earthing, they must still have protective earthing.