The isolator'ssupply capabilityand loop voltage drop must be calculated: the open-circuit voltage, loaded voltage, and maximum output current must meet the transmitter's requirements; otherwise the instrument will be under-voltage and the signal distorted.
The QISON SC3042 provides isolated power to 2/3-wire transmitters on the input side, with an open-circuit voltage ≤26 V and an output voltage ≥22 V at 20 mA. When ordering, confirm whether the transmitter is 2-wire or 3-wire and whether the power supply capability is sufficient.