Troubleshoot in the order "power—input—output—load": first confirm the power supply is stable; then check whether the input signal is within range; then check whether the output matches the range; finally verify whether the load exceeds limits and whether grounding and shielding are good.
If an isolator is used to power a two-wire transmitter, also confirm that the supply voltage is sufficient under load (e.g. SC3042 outputs ≥22 V at 20 mA).