What regulations must be followed for the installation and maintenance of intrinsically safe equipment

Standards & Certification · 23 November 2026

The main basis for installation and maintenance is GB/T 3836.15 (design, selection and installation) and GB/T 3836.16 (inspection and maintenance), corresponding to IEC 60079-14 and 60079-17.

Six key points at the installation stage

  • Work according to the design drawings; do not change cable routes and lengths without authorisation;
  • Intrinsically safe circuits and non-intrinsically safe circuits shall be laid separately, with spacing and barriers meeting the requirements;
  • Intrinsically safe cables should use a blue outer sheath and be marked at both ends;
  • Zener barriers shall be earthed via a dedicated conductor to the busbar, not daisy-chained;
  • Cable entries shall use sealing glands compliant with the IP rating;
  • After installation, verify parameters circuit by circuit and keep records.

Three requirements during the maintenance phase

  • Periodic inspection: Carry out visual, detailed and close inspections at intervals specified by the standards, focusing on the enclosure, sealing, earthing and labelling;
  • Change management: Replacing instruments, extending cables or adding junction boxes all require recalculation and updated records;
  • Personnel competence: Personnel engaged in explosion-protected electrical installation and servicing shall receive appropriate training and possess the corresponding competence.

Boundaries of opening enclosures while energised:Intrinsically safe equipment may be opened while energised, provided thatthe circuit is genuinely an intrinsically safe circuit and operates within the certified parameters. If non-intrinsically safe wiring is mixed into the circuit, or the safety barrier has failed, the premise of "opening while energised is permitted" no longer holds. Confirming circuit identity before maintenance is more important than remembering the conclusion that "intrinsically safe equipment may be opened".

← Back to Knowledge Sharing

Online customer service
Online customer service Scan or click to contact directly
Contacts
Miss Chen(Safety barriers, isolators, surge protectors)
Ms Chen Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:2501529964

Phone:17717626508

Email:chenjing@qishan-sh.com

Miss Lu(Field Instruments, Valve Accessories, Terminal Blocks)
Ms Lu Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:1695457483

Phone:13636420802

Email:lhm@qishan-sh.com

Mr. Ye(Technical Support, After-Sales Service)

QQ:97010638

Phone:15800474322

Email:web@qishan-sh.com

Online Message

Please fill in the name

Please fill in a valid contact phone number (7-20 digits)

Please enter a valid email address

Please enter the requirement description (at least 10 characters)