What are the cable requirements for intrinsically safe circuits?

Safety Barriers · 17 November 2026

The distributed capacitance and inductance of intrinsically safe circuit cablesdistributed capacitance and inductancemust be included in the circuit parameters and must not exceed the Co and Lo permitted by the safety barrier. Intrinsically safe dedicated cables (usually identified in blue) should be used, laid separately from non-intrinsically safe circuits with maintained spacing, and the shield should be single-point earthed as specified.

For long-distance installation, the cable parameters must especially be calculated; if necessary, use low-capacitance low-inductance cables or shorten the distance.