Co is the maximum external capacitance permitted by the safety barrier for connection to the hazardous areamaximum external capacitance, and Lo is the permittedmaximum external inductance. The sum of the cable's distributed capacitance/inductance and the field instrument's input parameters must not exceed Co and Lo; otherwise the circuit's stored energy may exceed the safety limit and compromise intrinsic safety performance.

Cable parameters must be verified especially for long-distance runs: ensure "safety barrier Co/Lo ≥ total cable + instrument capacitance/inductance" for the intrinsically safe circuit to be valid.