The core parameters include: maximum permissible voltage Um, maximum output voltage Uo, maximum output current Io, maximum output power Po, permissible external capacitance Co and external inductance Lo. The selection principle is that the safety barrier output energy must not exceed the withstand capability of the field instrument, and the actual loop capacitance and inductance must not exceed the permissible Co and Lo.
For isolators, also check the supply voltage (e.g. 24 V DC), input/output signal type, number of channels, and whether functions such as LFD, HART and SIL are supported.