First confirm whether the actual line voltage exceeds the SPD rated voltage (an undersized selection will cause false tripping); then check whether the wiring forms an abnormal loop with the shield/earth; then measure whether the SPD has degraded; finally check whether there is a continuous transient interference source in the line.
When it is confirmed to be a selection issue, replace the SPD with a suitable voltage rating rather than suppressing the alarm.