When LFD (line fault detection) reports a broken wire/short circuit, first confirm whether the power supply to the field instrument in the hazardous area (such as a proximity switch or NAMUR sensor) is normal; then check the circuit cable for open circuits, short circuits or abnormal shield earthing; then verify the terminating resistor and NAMUR settings.
During troubleshooting, do not open the cover or short-circuit the circuit while energised in the hazardous area; after clearing the fault, confirm that LFD has returned to normal.