C7000 process controller
16-channel touchscreen process controller, supports PID cascade and program segment control, dual battery redundancy, includes Ethernet communication.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
The C7000 is a 16-channel touchscreen controller supporting universal analogue inputs including current, voltage, RTD, thermocouple and frequency signals, and can provide up to 8 channels of distribution output. The distribution outputs share terminals with the measurement channels for convenient wiring, and the wiring method can be viewed on the instrument interface.
The controller features computation functions, PID cascade control and program segment control, making it suitable for a variety of complex control scenarios; its unique event and statistics functions can record special situations during batch production (such as recording important parameters when temperature or pressure exceeds limits) and perform statistical analysis of maximum, minimum and average values. The instrument adopts a dual battery redundant design, so data is not lost when batteries are replaced, and battery life is 5–10 years.
| Parameter Name | Technical Specifications |
|---|---|
| Channel configuration | |
| Analogue input | 16-channel |
| Analogue output | 4 channels |
| Digital input | 3-channel |
| Relay output | 16-channel |
| Frequency input | 3-channel |
| Time-proportional output | 8-channel |
| Signal input | |
| Current | 4~20mA, 0~20mA |
| Voltage | -10~10V, -100~100mV |
| Frequency | 0~10kHz (0~32V) |
| Thermistors | Pt100, JPt100, PT1000, Cu50 |
| Thermocouples | B, E, J, K, S, T, N, R, WRe5-26, WRe3-25, etc. |
| Digital | 0~32V |
| Control functions | |
| Control mode | PID cascade control, program segment control |
| Computation functions | Flow calculation with temperature and pressure compensation, totalisation |
| Events and statistics | Records batch abnormal parameters, calculates maximum/minimum/average values |
| Redundant | Dual battery redundancy, data retained during battery replacement (battery life 5–10 years) |
| Accuracy and communication | |
| Sampling period | 0.5 s |
| Measurement accuracy | ±0.2% |
| Communication | RS232/RS485 and Ethernet |
| Data interface | USB flash drive |
| Power distribution specification | 200mA/24V |
| Isolation | 400VAC between channels; 1500VAC between channel and ground |
| Power supply and environment | |
| Power Supply | AC (100~240) V, (47~63) Hz |
| Power dissipation | ≤30VA |
| Operating Temperature | (-20~60)℃ |
| Relative Humidity | (5–95)%RH |
| Fuse specification | 250VAC/3A, slow-blow type |
| Dimensions | |
| Dimensions | 191.5mm×159.5mm×195mm |
| Hole size | 138mm×138mm |
| Mounting panel thickness | (1.5–8.0)mm |
- 16-channel universal input, 4 analogue outputs + 16 relay outputs
- Supports PID cascade control, suitable for complex loops such as temperature, pressure and flow
- Program segment control, enables ramp–soak–ramp-down segmented curves
- Event and statistics functions, records batch abnormalities and performs maximum/minimum/average analysis
- Dual battery redundancy design, data retained during battery replacement
- RS232/RS485 and Ethernet communication, supporting USB flash drive export and printing
Reactor temperature cascade control
PID cascade loop controls jacket temperature; program segments implement ramp–soak–ramp-down process curves.
Batch production statistics
Event and statistics functions record batch abnormal parameters and output maximum, minimum and average reports.
No documents uploaded yet.
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232
- Email inquiry web@qishan-sh.com