HiSHPTB/32/HONB-AO-R-01 32-channel HART termination board
Replaces TDC 3000 FTA, short-circuit protection, HART analogue output filter, redundant PCS wiring.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
Pepperl+Fuchs HiSHPTB/32/HONB-AO-R-01 HART termination board, replacement for TDC 3000 FTA, short-circuit protection, HART analogue output filter, redundant PCS wiring, redundant power supply connection.
Part of the HART Interface Devices series, used for communication access, signal tapping and commissioning configuration between DCS/PLC control systems and HART field instruments, supporting HART protocol (including WirelessHART) multiplexing, loop conversion and filtering, and compatible with mainstream barriers and termination boards.
| Parameter Name | Technical Specifications |
|---|---|
| Power Supply | |
| Rated Voltage | 24 V DC |
| Fuse protected | 315 mA, 5 x 20 mm (0.2 x 0.8 inch) |
| Power dissipation | 0.7 W, (with multiplexer) |
| Reverse polarity protection | 是 |
| HART signal channel (intrinsically safe) | |
| Number of Channels | 32 unbalanced signal loops |
| Redundant | |
| Power supply | 是 |
| Electrical Isolation | |
| HART signal channels | 30 V DC |
| Ambient Conditions | |
| Ambient Temperature | 0 … 55 °C (32 … 131 °F) |
| Relative Humidity | 5 … 90 %, non-condensing |
| Mechanical parameters | |
| Core cross-section | 2.5 mm² (16 AWG) |
| Connection | field side: 5.08 mm removable screw terminals, control side: 50-pin Centronics plug, RS-485 interface: 5.08 mm removable screw terminals, power: removable screw terminals |
| Weight | Approx. 500 g |
| Dimensions | 333 x 127 x 190 mm (13.1 x 5 x 7.5 inch) (W x H x D), depth including HiDMux2700 |
| Height | 127 mm |
| Width | 333 mm |
| Depth | 190 mm |
| Installation Method | DIN rail mounting |
| General information | |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals and manuals within the applicable scope. For related information, see www.pepperl-fuchs.com. |
- Replacement for TDC 3000 FTA
- Short-circuit protection
- HART analogue output filter
- Redundant PCS wiring
- Redundant power supply connection
- Field terminal block compatible with Honeywell FTA
- Honeywell type B mounting dimensions
Petrochemical Plant
HART field instrument commissioning and configuration communication
Power Energy System
DCS system HART multiplexer access
Process Automation
HART signal filtering and tapping between control room and field instruments
Documents not uploaded. Please fill in the information row by row in the 'Product Details Field' panel under 'File Name | Download Address | File Size'.
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232
- Email inquiry web@qishan-sh.com