IsoPAQ-610 HART Repeater Power Supply
The IsoPAQ-610 repeater power supply is used to supply and isolate two-wire/three-wire smart transmitters and active sensor signals with HART communication.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
The IsoPAQ-610 repeater power supply is used to supply and isolate two-wire/three-wire smart transmitters and active sensor signals with HART communication.
It supplies the transmitter and transmits the measurement signal to the output with high-precision electrical isolation. The measurement input can also receive active 0/4…20 mA signals from four-wire transmitters.
In addition to the analogue signal, the IsoPAQ-610 can transmit the HART communication data protocol. Bidirectional communication with field devices is possible at any point on the wiring.
Auxiliary power can be supplied via terminals or the optional In-Rail-Bus rail bus connector. A green LED on the front panel monitors power status.
| Parameter Name | Technical Specifications |
|---|---|
| Technical specifications | |
| Input Signal | 0/4…20 mA (4…20 mA with HART signal) |
| Input Impedance | 50 Ω |
| Overload | 50 mA / 30 V |
| Transmitter supply (Tx) | 16 V (open-circuit voltage/short-circuit current < 22 V/35 mA) |
| Communication signal | Bidirectional HART transmission, internal AC impedance 250 Ω |
| Output Signal | 0/4…20 mA (4…20 mA with HART signal) |
| Load | ≤ 12 V (600 Ω at 20 mA) |
| Linear transmission range | –1 … +110 % |
| Residual ripple | < 10 mV rms |
| Transmission error | < 0.1 % full scale |
| Temperature coefficient 1) | < 100 ppm/K |
| Cut-off frequency (-3 dB) | 100 Hz, >2.5 kHz HART signal |
| Response time T99 | 7 ms |
| Test voltage | 3 kV AC, 50 Hz, 1 min. Input against output against power supply |
| Operating voltage (basic insulation) | 600 V AC/DC for overvoltage category II and contamination class 2 acc. to EN 61010-1 |
| Protection against hazardous body currents | Reinforced insulation acc. to EN 61010-1 up to 300 V AC/DC for overvoltage category II and contamination class 2 between input and output and power supply. |
| Ambient Temperature | Operation – 25 °C to + 70 °C (– 13 to + 158 °F) Transport and storage – 40 °C to + 85 °C (– 40 to + 185 °F) |
| Power Supply | 24 VDC 16.8 … 31.2 V DC, approx. 1.3 W |
| Electromagnetic compatibility | EN 61326-1 |
| Structure type | 62 x 96.5 x 107 mm, protection class IP 20, mounted on 35 mm DIN rail acc. to EN 60715 |
| Weight | Approx. 70 g |
- The IsoPAQ-610 repeater power supply is used to supply and isolate two-wire/three-wire smart transmitters and active sensor signals with HART communication.
- It supplies the transmitter and transmits the measurement signal to the output with high-precision electrical isolation. The measurement input can also receive active 0/4…20 mA signals from four-wire transmitters.
- In addition to the analogue signal, the IsoPAQ-610 can transmit the HART communication data protocol. Bidirectional communication with field devices is possible at any point on the wiring.
Process loop signal isolation
Interfaces two-wire transmitters with the control system in DCS/PLC analogue loops, eliminating measurement errors caused by ground potential differences and earth loops.
Hazardous area signal conditioning
In refining and petrochemical units, 4–20 mA signals are isolated and distributed to the control system and safety interlock loops, ensuring a reliable signal chain.
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232
- Email inquiry web@qishan-sh.com