IsoPAQ-632 signal splitter/repeater
The IsoPAQ-632 signal splitter/repeater is used for the isolation, conversion and distribution of 0/4…20 mA, 0/1…5 V and 0/2…10 V standard signals.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
The IsoPAQ-632 signal splitter/repeater is used for the isolation, conversion and distribution of 0/4…20 mA, 0/1…5 V and 0/2…10 V standard signals. The measuring input can also provide loop power for two-wire transmitters.
Input and two isolated outputs can be conveniently configured via DIP switches. Due to the calibrated range selection, no further adjustment is required.
Auxiliary power can be supplied via terminals or the optional In-Rail-Bus rail bus connector. A green LED on the front panel monitors power status.
| Parameter Name | Technical Specifications |
|---|---|
| Technical specifications | |
| Input signal (calibrated, switchable) | 0 … 20 mA, 0 … 10 V, 0 … 5 V 4 … 20 mA, 2 … 10 V, 1 … 5 V |
| Input Impedance | Current input: ≤ 35 Ω Voltage input: ≥ 100 kΩ |
| Overload | Current input: < 50 mA Voltage input: < 30 V |
| Transmitter supply Tx | 16 V (open circuit voltage/short circuit current ≤ 22 V/35 mA) |
| Output signal (calibrated, switchable) | 0 … 20 mA, 0 … 10 V, 0 … 5 V 4 … 20 mA, 2 … 10 V, 1 … 5 V |
| Load | Current output: ≤ 6 V (300 Ω at 20 mA) Voltage output: ≤ 5 mA (2 kΩ at 10 V) |
| Linear transmission range | –1 … +110 % |
| Residual ripple | < 10 mV rms |
| Transmission error | < 0.1 % full scale |
| Temperature coefficient | < 100 ppm/K |
| Cut-off frequency (-3 dB) | -3 dB 5 kHz |
| Response time T99 | 150 µs |
| Test voltage | 3 kV AC, 50 Hz, 1 min. Input against Output 1 against Output 2 against power supply |
| Operating voltage (basic insulation) | 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 |
| Protection against electric shock | Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. |
| Ambient Temperature | Operation – 25 °C to + 70 °C (– 13 to + 158 °F) Transport and storage – 40 °C to + 85 °C (– 40 to + 185 °F) |
| Power Supply | 24 V DC voltage range 16.8 … 31.2 V DC, approx. 1.4 W |
| Electromagnetic compatibility | EN 61326-1 |
| Structure type | 62 x 96.5 x 107 mm, protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715 |
| Weight | Approx. 70 g |
- The IsoPAQ-632 signal splitter/repeater is used for the isolation, conversion and distribution of 0/4…20 mA, 0/1…5 V and 0/2…10 V standard signals. The measuring input can also provide loop power for two-wire transmitters.
- Input and two isolated outputs can be conveniently configured via DIP switches. Due to the calibrated range selection, no further adjustment is required.
- Auxiliary power can be supplied via terminals or the optional In-Rail-Bus rail bus connector. A green LED on the front panel monitors power status.
Process loop signal isolation
Interfaces two-wire transmitters with the control system in DCS/PLC analogue loops, eliminating measurement errors caused by ground potential differences and earth loops.
Hazardous area signal conditioning
In refining and petrochemical units, 4–20 mA signals are isolated and distributed to the control system and safety interlock loops, ensuring a reliable signal chain.
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232
- Email inquiry web@qishan-sh.com