KFD2-HLC-Ex1.D Type 1-channel HART circuit converter

Product Model KFD2-HLC-Ex1.D

Product Brand

Product Category Industrial Safety and Signal Conditioning Modules / HART Interface Devices, Industrial Safety and Signal Conditioning Modules

Application Industry Power Energy, Petroleum Chemical Industry, Process Automation

1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input, with transmitter power supply, usable as signal splitter (1 input, multiple outputs).

Inquire Now
  • Original Factory Genuine, Tenfold Compensation for Counterfeits
  • Full Machine Warranty, Lifetime Maintenance
  • In Stock, Shipped on the Same Day

Pepperl+Fuchs KFD2-HLC-Ex1.D HART loop converter, 1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, can be used as signal splitter (1 input, multiple outputs), 3 analogue outputs 4…20 mA.

Part of the HART Interface Devices series, used for communication access, signal tapping and commissioning configuration between DCS/PLC control systems and HART field instruments, supporting HART protocol (including WirelessHART) multiplexing, loop conversion and filtering, and compatible with mainstream barriers and termination boards.

KFD2-HLC-Ex1.D 1-channel HART loop converter technical data
Parameter Name Technical Specifications
General specifications
Signal type Analogue input
Power Supply
Connection Power Rail or terminals 23+, 24-
Rated Voltage 19 ... 30 V DC
Rated current approx. 120 mA (at 24 V DC)
Power dissipation 2.3 W
Power dissipation 2.9 W
HART signal channel (intrinsically safe)
Conformity HART field device input (protocol version 5–7)
Interface
Programming interface Programming socket
Input
Connection side Field side
Connection Terminals 1, 2, 3, 4, 5, 6
Open-circuit voltage/short-circuit current Typically 24 V, 28 mA
Input resistance 250 Ω, 5 % (terminals 2, 3 and jumper 5, 6)
Available voltage ≥ 15.5 V at 20 mA, short-circuit protected
Output
Connection side Control side
Connection output I: terminals 7, 8, 9, output II: terminals 13, 14, 15, output III: terminals 19, 20, 21
Output Signal Analogue
Voltage range 5 … 30 V, sink mode (powered by external supply)
Current range 4 … 20 mA, (source or sink mode)
Load Max. 650 Ω, source mode
Fault signal Per NAMUR NE43: underrange alarm I ≤ 2 mA, overrange alarm I ≥ 21.5 mA, or hold measured value
Other outputs HART communicator on terminals 22, 24
Collective fault message Power Rail and LED red
Transfer characteristics
Resolution Max. 2 µA
Accuracy < 20 µA, typically 10 µA
Ambient temperature effect < ± 2 µA/K
Measurement duration/response delay HART telegram acquisition time + 100 ms
Electrical Isolation
output I/II/III/supply Functional insulation according to IEC 62103, rated insulation voltage 50 Veff
Indication/setting
Display elements LED, display
Operating elements Control panel
Configuration Via operating buttons or PACTware
Marking Reserved marking area on the front
Directive conformity
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient Conditions
Ambient Temperature −20 … 60 °C (−4 … 140 °F)
Mechanical parameters
Degree of protection IP20
Connection Screw terminals
Weight 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W × H × D), enclosure type C2
Installation Method Mounts on 35 mm DIN mounting rail in accordance with EN 60715:2001
Hazardous area application data
EU Type Examination Certificate BASEEFA 07 ATEX 0174
Marking II (1)G [Ex ia Ga] IIC, Ex II (1)D [Ex ia Da] IIIC
Maximum safety voltage 253 V AC (note: rated voltage may be lower)
Device Terminals 1, 4/3 (with terminals 4 and 5 linked)
Voltage 25.2 V
Current 104.9 mA
Power 0.661 W
Internal capacitance 1.1 nF
Internal inductance 0 mH
Device Terminals 2, 5/3
Voltage < 28 V
Power < 1.33 W
Voltage 1.1 V
Current 11.9 mA
Power 4 mW
Internal capacitance 0 µF
outputs I, II, III terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 non-intrinsically safe
Maximum safety voltage 253 V (Attention! Um is no rated voltage.)
Certificate PF 07 CERT 1142 X
Marking II 3G Ex nA IIC T4 Gc
Input/other circuits safe electrical isolation according to IEC/EN 60079-11, voltage peak value 375 V
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020, EN 60079-11:2012, EN 60079-15:2010
International approvals
Control drawing 116-0129
IECEx certificate IECEx BAS 07.0047
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals and manuals within the applicable scope. For related information, see www.pepperl-fuchs.com.
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • HART field device input with transmitter power supply
  • Can be used as signal splitter (1 input, multiple outputs)
  • 3 analogue outputs 4…20 mA
  • Outputs support sink/source mode
  • Configurable via keypad

Petrochemical Plant

HART field instrument commissioning and configuration communication

Power Energy System

DCS system HART multiplexer access

Process Automation

HART signal filtering and tapping between control room and field instruments

Need selection advice or bulk quotation?

Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.

Please fill in the name

Please fill in a valid contact phone number (7-20 digits)

Please enter a valid email address

Inquire about the product

KFD2-HLC-Ex1.D · KFD2-HLC-Ex1.D 1-channel HART loop converter

Please enter the requirement description (at least 10 characters)

Online customer service
Online customer service Scan or click to contact directly
Contacts
Miss Chen(Safety barriers, isolators, surge protectors)
陈小姐 个人微信二维码

Scan WeChat QR code to add personal WeChat

QQ:2501529964

Phone:17717626508

Email:chenjing@qishan-sh.com

Miss Lu(Field Instruments, Valve Accessories, Terminal Blocks)
卢小姐 个人微信二维码

Scan WeChat QR code to add personal WeChat

QQ:1695457483

Phone:13636420802

Email:lhm@qishan-sh.com

Mr. Ye(Technical Support, After-Sales Service)

QQ:97010638

Phone:15800474322

Email:web@qishan-sh.com

Online Message

Please fill in the name

Please fill in a valid contact phone number (7-20 digits)

Please enter a valid email address

Please enter the requirement description (at least 10 characters)