NS14 Potentiometer Transmitter
Input: 2-wire/3-wire potentiometer (0–10 kΩ); isolated transmission output 0/4–20 mA, 0/1–5 V, 0/2–10 V; supports 1-in/1-out, 1-in/2-out, 2-in/2-out, 1-in/3-out, optionally with communication or alarm.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
Potentiometer transmitter: inputs a 3-wire potentiometer signal and converts it, with isolation, into a current or voltage output. Features online fault self-diagnostics; the potentiometer zero and span, output signal type, and output mode on signal fault can be configured via PC or handheld programmer.
| Parameter Name | Technical Specifications |
|---|---|
| Power supply and power consumption | |
| Power Supply | 18 V DC–32 V DC (independent supply); 12 V DC–30 V DC (loop supply) |
| Power consumption | ≤0.7 W (24 V single-channel full load); ≤1.3 W (24 V dual-channel full load) |
| Input characteristics | |
| Input Signal | 2-wire, 3-wire potentiometer 0 kΩ–10 kΩ |
| Output and load | |
| Output Signal | Current: 0/4–20mA (dual-channel supports passive output); Voltage: 0/1–5V, 0/2–10V |
| Permissible load | Current active RL≤550Ω; passive RL<[(U-3)/0.02]Ω; voltage RL≥1MΩ/≥2MΩ |
| Accuracy and response | |
| Conversion accuracy | 0.1%F.S. (25°C±2°C) |
| Temperature drift | 40ppm/°C |
| Response time | ≤500ms |
| Isolation and Environment | |
| Electromagnetic compatibility | IEC 61326-3-1 |
| Dielectric strength | ≥1500V AC (between input/output/power supply) |
| Insulation resistance | ≥100MΩ (between input/output/power supply) |
| Operating Temperature | -20°C~+60°C |
| Storage Temperature | -40°C~+80°C |
- 2-wire/3-wire potentiometer input, configurable zero and span
- Current/voltage multi-type output, supports passive output
- DIN-rail mounting, three-way isolation of input, output and power supply, dielectric strength ≥1500V AC, EMC IEC 61326-3-1.
Isolated transmission of potentiometer valve position feedback
Converts the 3-wire potentiometer valve position feedback signal of an electric valve into 4–20 mA for connection to the control system, enabling remote valve position transmission
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232
- Email inquiry web@qishan-sh.com