SC3011 switch input isolator (one in, one out, relay output)
Single-channel switch input isolator: dry contact/NAMUR proximity switch input, isolated and converted to relay output; three-port isolation, DIP switches configurable for same/inverted logic and line fault monitoring.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
Switch input isolator, input dry contact or NAMUR proximity switch signal, isolated and converted to relay/transistor output. DIP switches can be used to set output and input same-phase or inverted logic control (default same-phase), set line fault monitoring on or off (default on, LED flashes on line fault), and set the second output function (as relay/transistor output or as fault alarm output). This product requires independent power supply, with three-port isolation of input, output and power.
Note:Three-port isolation of input, output and power. 24V DC independent power supply (note polarity of power terminals, module has power reverse protection); input side connects to dry contact switch or NAMUR proximity switch; output side is relay contact, can drive ≤40mA load, allowable load 250VAC/2A or 30VDC/2A. Module indicators: green power indicator, red fault signal, yellow channel status. When line fault monitoring is on, input disconnection (≤50μA) or short circuit (≥6.5mA) will cause the output relay to open and the red indicator to flash. All terminals are hot-swappable. Specific terminal numbers are subject to the silkscreen on the module side.
Ordering information:
- This product requires independent power supply (18V DC~32V DC), system power supply configuration must be confirmed when ordering.
- Output logic (same-phase/inverted), line fault monitoring, and second output function are set via DIP switches, default: same-phase, fault monitoring on.
| Parameter Name | Technical Specifications |
|---|---|
| Power supply and power consumption | |
| Power Supply | 18V DC ~32V DC power reverse protection |
| Power consumption | 1W |
| Input characteristics | |
| Input Signal | Dry contact or NAMUR proximity switch |
| Switching characteristics | Input current>2.1mA, output relay closed, channel indicator yellow steady on; input current<1.2mA, output relay open, channel indicator yellow off |
| Open-circuit voltage | Approx. 8.5V |
| Short-circuit current | Approx. 8.5mA |
| Line fault | Input current≤50μA, input wire break detected, output relay open; input current≥6.5mA, input short circuit detected, output relay open; channel indicator red flashing |
| Output and load | |
| Output Signal | Relay contacts |
| Permissible load | 250VAC/2A or 30VDC/2A |
| Drive current | ≤40mA |
| External voltage | <40V DC |
| Switching frequency | <20ms |
| Isolation and electromagnetic compatibility | |
| Electromagnetic compatibility | <10Hz |
| Dielectric strength | ≥1500V AC (between input/output/power supply) |
| Insulation resistance | ≥100MΩ (between input/output/power supply) |
| Environmental and Mechanical | |
| IP Protection | IP20 |
| Operating Temperature | -20℃~+60℃ |
| Storage Temperature | -40℃~+80℃ |
| Dimensions | 12.8mm×110mm×117mm (W×H×D) |
| DIP switch settings | |
| DIP switch | S1~S4 (module marked 51, 52, 53, 54): same-phase/inverted logic (default same-phase), line fault monitoring switch (default on), second output function (SC3012 is relay/transistor output or fault alarm output) |
- Dry contact or NAMUR proximity switch input, isolated and converted to relay contact output
- DIP switches set same-phase/inverted logic (default same-phase), line fault monitoring (default on, LED flashes on fault)
- Input disconnection (≤50μA)/short circuit (≥6.5mA) online monitoring, output opens and indicator flashes on fault
- Three-port isolation of input, output and power, forming a fully floating system, no grounding required
- Allowable load 250VAC/2A or 30VDC/2A, drive current ≤40mA
- DIN rail mounting, hot-swappable terminals, 12.8mm compact width
Dry contact signal isolated connection to DCS/PLC
Dry contact (passive contact) or NAMUR proximity switch signal connected to DCS/PLC switch input channel, relay normally-open contact also serves as fault alarm output, electrical isolation between field and control room
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232
- Email inquiry web@qishan-sh.com