SC3044 Analogue Input Isolator (Dual Channel, HART Pass-through)
Dual-channel current input isolator: two 4-20mA channels each isolated and transmitted, supporting 2 active/passive outputs and bidirectional HART pass-through.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
Dual-channel configuration, two 0/4–20mA input signals each isolated and transmitted, supporting 2 active/passive 4-20mA outputs and bidirectional HART digital signal transmission. Requires independent power supply, with three-port isolation between input, output and power supply.
Note:Three-port isolation between input, output and power supply. 24V DC independent power supply; each of the two inputs connects to a 2-wire/3-wire transmitter (isolated supply provided, open-circuit ≤26V, ≥22V at 20mA); the two outputs are 4-20mA, configurable as active or passive current output, RL≤550Ω; bidirectional HART digital signal transmission. Module indicators: green power indicator, red fault signal. All terminals are hot-swappable. Refer to the module side silkscreen for specific terminal numbers.
Ordering information:
- Requires independent power supply (18V DC–60V DC).
- Confirm whether each output requires active or passive mode when ordering.
| Parameter Name | Technical Specifications |
|---|---|
| Power supply and power consumption | |
| Power Supply | 18V DC–60V DC |
| Power consumption | ≤2.5W (24V, two in/two out at full load output) |
| Input characteristics | |
| Input Signal | 0/4–20mA |
| Input Impedance | 50Ω |
| Distribution voltage | Open-circuit voltage ≤26V, output voltage ≥22V at 20mA |
| Output and load | |
| Output Signal | 0/4–20mA |
| Permissible load | 0/4–20mA: RL≤550Ω |
| Accuracy and response | |
| Conversion accuracy | 0.1%F.S. |
| Temperature drift | 30ppm/℃ |
| Response time | ≤2ms |
| Isolation and electromagnetic compatibility | |
| Electromagnetic compatibility | IEC 61326-3-1 |
| Dielectric strength | ≥1500V AC (between input/output/power supply) |
| Insulation resistance | ≥100MΩ (between input/output/power supply) |
| Environmental and Mechanical | |
| IP Protection | IP20 |
| Operating Temperature | -20℃~+60℃ |
| Storage Temperature | -40℃~+80℃ |
| Dimensions | 17.8mm×110mm×117mm (W×H×D) |
- Dual channel, two in/two out, two inputs each isolated and transmitted
- Two 4-20mA outputs configurable as active or passive, for flexible connection to different supply topologies
- Provides isolated power supply for 2/3-wire transmitters (open-circuit ≤26V)
- Supports bidirectional HART digital signal transmission
- Centralised isolation of dual-loop current signals (e.g. dual-parameter pressure/differential pressure)
- 17.8 mm width, DIN rail mounting
Centralised isolation of dual-loop current signals
Centralised isolation of dual-loop current signals (e.g. dual-parameter pressure/differential pressure); the two outputs are configurable as active/passive for flexible connection to DCS/PLC channels with different supply topologies
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232
- Email inquiry web@qishan-sh.com