TCP-LBF-IA1.36.IE* surge protector
Plug-in, installed between device coupler and trunk cable, intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus or general-purpose (non-Ex), optional wear diagnostics, shield earthed via gas discharge tube.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
Pepperl+Fuchs TCP-LBF-IA1.36.IE* surge protector, plug-in, installed between device coupler and trunk cable, intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus or general-purpose (non-Ex), optional wear diagnostics, shield earthed via gas discharge tube, for FOUNDATION Fieldbus H1 and PROFIBUS PA.
For lightning and switching overvoltage protection of signal lines, power lines and fieldbus lines between hazardous areas and safe areas, DIN rail or field enclosure mounting, directly connected in series in instrument loops, DCS/PLC I/O and bus trunk/spur lines.
| Parameter Name | Technical Specifications |
|---|---|
| General specifications | |
| Design/Installation | Cabinet mounting |
| Hazardous area installation | Zone 1, Div. 1 |
| Fieldbus connection | |
| Own current consumption | max. 6 mA (for version TCP-LBF-IA1.36.IE.1), max. 0 mA (for version TCP-LBF-IA1.36.IE.0) |
| Indicating/operating elements | |
| LED ERR | flashing green: status OK, flashing red: maintenance required, (for version TCP-LBF-IA1.36.IE.1) |
| Electrical Data | |
| Rated Voltage | 36 V |
| Rated current | 600 mA |
| Line/line | max. 50 V class B2 10/700 µsec, 25 A, max. 50 V class C1 8/20 µsec, 300 A, max. 55 V class C2 8/20 µsec, 5 kA, max. 46 V class C3 1 kV/µsec, 10 A |
| Line/earth | max. 1060 V class B2 10/700 µsec, 50 A per line, max. 800 V class C1 8/20 µsec, 300 A per line, max. 1.5 kV class C2 8/20 µsec, 5 kA per line, max. 1.3 kV class C3 1 kV/µsec, 50 A per line, max. 1080 V class D1 10/350 µsec, 500 A per line |
| indirect shield grounding (via gas discharge tube) | max. 500 V class B2 10/700 µsec, 100 A, max. 600 V class C1 8/20 µsec, 500 A, max. 720 V class C2 8/20 µsec, 10 kA, max. 550 V class C3 1 kV/µsec, 100 A, max. 570 V class D1 10/350 µsec, 1 kA |
| Line/line | Max. 1 ns |
| Line/earth | Max. 100 ns |
| shield-to-ground | Max. 100 ns |
| Overstress fault mode | According to IEC 61643-21 line inoperable mode 3 |
| Line series resistance | 2 Ω ± 5 % |
| Per line | 5 kA class C2 8/20 µsec |
| indirect shield grounding (via gas discharge tube) | 1 kA class D1 10/350 µsec, 10 kA class C2 8/20 µsec |
| Directive conformity | |
| Directive 2014/30/EU | EN 61326-1:2013 |
| Standards compliance | |
| Electromagnetic compatibility | NAMUR NE 21 |
| Degree of protection | IEC 60529 |
| Fieldbus standard | IEC 61158-2 |
| Climatic conditions | IEC 60721 |
| Shock resistance | EN 60068-2-27 |
| Vibration Resistance | EN 60068-2-6 |
| Surge protection | IEC 61643-21 |
| Ambient Conditions | |
| Ambient Temperature | −40 … 70 °C (−40 … 158 °F) |
| Storage Temperature | −40 … 85 °C (−40 … 185 °F) |
| Relative Humidity | ≤ 95 % non-condensing |
| Shock resistance | 15 g 11 ms |
| Vibration Resistance | 1 g, 10 … 150 Hz |
| Corrosion resistance | Severity level G3 according to ISA-S71.04-1985 |
| Mechanical parameters | |
| Wiring Type | Screw terminals |
| Core cross-section | Flexible conductor 2.5 mm2, solid conductor max. 4 mm2 |
| Housing material | Polyamide PA 6.6 |
| Degree of protection | IP20 |
| Weight | 80 g |
| Earthing | M4 screw and external grounding rail |
| Hazardous area application data | |
| EU Type Examination Certificate | SIRA 12 ATEX 2128X |
| Marking | II 1G Ex ia IIC T4 |
| Voltage | 24 V |
| Current | 500 mA |
| Internal capacitance | 2 nF |
| Internal inductance | 0.1 µH |
| Certificate | SIRA 12 ATEX 4176X |
| Marking | II 3G Ex nAc IIC T4, [exsign] II 3G Ex ic IIC T4 |
| Voltage | 33 V |
| Current | 600 mA |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020, EN 60079-11:2012, EN 60079-15:2010 |
| Supplementary information | FISCO field device |
| International approvals | |
| CSA certification | CoC 2595441 |
| Control drawing | 116-0365 |
| Certification scope | Class I, Division 1, Groups A, B, C, D T4, Class I, Zone 1, Ex ia IIC T4, Class I, Zone 2, Ex ic IIC T4, Class I, Zone 1, AEx ia IIC T4, Class I, Zone 2, AEx ic IIC T4, Class I, Division 2, Groups A, B, C, D T4, Class I, Zone 2, Ex nL IIC T4, Class I, Zone 2, Ex nA IIC T4, Class I, Zone 2, AEx nAc IIC T4 |
| IECEx certificate | IECEx SIR 12.0051X |
| IECEx marking | Ex ia IIC T4, Ex ic IIC T4, Ex nAc IIC T4 |
| General information | |
| Supplementary information | The declaration of conformity, certificate of conformity and instruction manual must be observed within the scope of application. For related information, see www.pepperl-fuchs.com. |
- pluggable, installed between device coupler and trunk cable
- Intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus or general-purpose (non-Ex)
- Optional wear diagnostics
- shield grounded via gas discharge tube
- For FOUNDATION Fieldbus H1 and PROFIBUS PA
- Indication via LED and advanced diagnostics
Petrochemical Plant
Lightning and overvoltage protection for instrument signal circuits
Power Energy System
Surge protection for power and signal lines
Process Automation
Surge protection for fieldbus trunk and spur lines
Documents not uploaded. Please fill in the information row by row in the 'Product Details Field' panel under 'File Name | Download Address | File Size'.
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232