What is "associated apparatus", and why must it be certified together with the field device?

Safety barriers and isolation technology · 23 November 2026

Associated Apparatus is equipment installed in the safe area that contains intrinsically safe circuits and may affect the energy in the hazardous area. Safety barriers are the most typical example. Its explosion protection marking usually includes square brackets, for example [Ex ia Ga] IIC— square brackets indicate "Associated Apparatus", meaning it is not itself used in the hazardous area but supplies power or transmits signals to equipment in the hazardous area.

Why a standalone certificate is not sufficient

The safety of an intrinsically safe system depends on the matching ofthree parameters: the output parameters of the safety barrier, the input parameters of the field device, and the distributed parameters of the connecting cable. Any one of these being compliant on its own does not mean the system is compliant.

Parameter pair Meaning Matching requirement
Uo ↔ Ui Maximum output voltage of safety barrier / maximum permissible input voltage of field device Uo ≤ Ui
Io ↔ Ii Maximum output current / maximum permissible input current Io ≤ Ii
Po ↔ Pi Maximum output power / maximum permissible input power Po ≤ Pi
Co ↔ Ci + Ccable Maximum permitted external capacitance / apparatus internal capacitance + cable capacitance Ci + Ccable ≤ Co
Lo ↔ Li + Lcable Maximum permitted external inductance / apparatus internal inductance + cable inductance Li + Lcable ≤ Lo

These five inequalities are the essence of "system certification" for intrinsically safe systems. The system certification issued by the manufacturer for a "safety barrier + a certain transmitter model" is essentially a pre-calculation and certification of these five inequalities, which the user can adopt directly; if there is no system certification, this calculation must be performed and documented by the user.

Engineering note:Changing the field instrument model, lengthening the cable, or adding terminals will alter one of the five inequalities. Any such change requires recalculation, rather than assuming "it was intrinsically safe before, so it still is after the change".

← Back to Knowledge Sharing

Online customer service
Online customer service Scan or click to contact directly
Contacts
Miss Chen(Safety barriers, isolators, surge protectors)
Ms Chen Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:2501529964

Phone:17717626508

Email:chenjing@qishan-sh.com

Miss Lu(Field Instruments, Valve Accessories, Terminal Blocks)
Ms Lu Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:1695457483

Phone:13636420802

Email:lhm@qishan-sh.com

Mr. Ye(Technical Support, After-Sales Service)

QQ:97010638

Phone:15800474322

Email:web@qishan-sh.com

Online Message

Please fill in the name

Please fill in a valid contact phone number (7-20 digits)

Please enter a valid email address

Please enter the requirement description (at least 10 characters)