Fail-safe meansthe system tends toward the safe side when a component fails. For a safety barrier, this is reflected in three levels of design.
- Component level: Zener diode short-circuit failure (rather than open-circuit), so that the voltage-limiting function remains after failure; the fuse then interrupts the continuous overcurrent.
- Circuit level: Redundant configuration of voltage-limiting elements (dual Zener in series), so that failure of either does not affect clamping; current-limiting resistors are of a non-flammable type with stable resistance.
- System level: When the barrier fails, the output tends towards a "no energy" state, the field instrument is de-energised, and the process side enters a safe state via interlock, rather than being maintained at an erroneous high-energy output.
This relates to the concepts of "Safe Failure Fraction (SFF)" and "Hardware Fault Margin (HWM)" in functional safety. If a barrier is used in an SIS loop, its Safety Integrity Level must be assessed in accordance with IEC 61508 / GB/T 20438, and the failure rate data provided by the manufacturer, such as λDD / λDU / SFF , must be checked.
Make the distinction clear:"Intrinsic safety" guarantees that no ignition occurs; "functional safety" guarantees that the device acts when it should. The two belong to different standards systems (GB/T 3836 series vs GB/T 20438 series), and their certifications are independent of each other. A product may satisfy only one or both — at the time of purchase, check the certificates separately; an explosion-proof certificate cannot substitute for a SIL certificate.