Two things must be checked in a barrier's SIL certification:Levelandapplicable configuration.
Level
Commonly marked as SIL 2 or SIL 3. Note that SIL 3 usually holds only under a specific configuration (e.g. single-channel SIL 2, redundant configuration up to SIL 3), as stated on the certificate. Do not design for SIL 3 merely because the product page advertises "supports SIL 3".
applicable configuration
- Single-channel / dual-channel / one-in-two-out: different structures have different failure rate data;
- Whether the assessment covers the combination of field device and barrier, or only the barrier itself;
- Certificate validity period and version number; parameters may change after revision.
| Certificate element | What to check | Common pitfalls |
|---|---|---|
| Standard basis | IEC 61508 or GB/T 20438 | Only an explosion protection certificate, mistaken for a functional safety certificate |
| SIL level | Explicitly states SIL 2 / SIL 3, with configuration prerequisites noted | Brochure states SIL 3, certificate covers only SIL 2 |
| Failure rate data | SFF, HFT, PFDavg or PFH | Missing data prevents loop verification calculations |
| Scope of assessment | Barrier body only, or including field instrument combination | Combination certificate expired or model discontinued |
Practical recommendation:When selecting for SIS loops, request combined assessment data from the manufacturer for the "safety barrier + field instrument" as a whole; this is more reliable than obtaining two separate SIL certificates — the safety integrity of a loop depends on the weakest link, not the simple addition of the levels of each link.