How to assess the transmission accuracy and load capability of a safety barrier

Safety barriers and isolation technology · 23 November 2026

These two specifications are often confused, but in fact one governs "how accurate" and the other governs "how much it can drive".

Transmission accuracy

Refers to the conversion error of the safety barrier for the signal, usually expressed as a percentage of full scale, with typical values of 0.1%–0.2% FS. It adds to the overall loop error chain: transmitter accuracy + safety barrier accuracy + acquisition card accuracy. The total system error is combined by root sum of squares or algebraic addition (depending on the standard and the manufacturer's convention); the smaller the safety barrier's share, the better.

Load capability

Refers to the maximum load resistance the safety barrier output can drive. For 4–20 mA output safety barriers, typical load capability is 0–500 Ω or 0–750 Ω. The direct symptom of exceeding the load limit is that the output current "cannot rise" in the high-signal range—at 20 mA it is actually only about 18 mA, and this worsens as the load increases.

Specification Typical value How to use it in selection
Transmission accuracy 0.1%–0.2% FS Compare with transmitter accuracy to avoid the barrier becoming the dominant error term
Temperature drift ≤ 0.01% FS/℃ For cabinets with large temperature fluctuations, convert based on the annual temperature difference
Load capability 0–500 Ω / 0–750 Ω Check whether "acquisition card input impedance + line resistance" falls within this range
Isolation withstand voltage 1.5 kV AC/min Compare against system insulation coordination requirements

A practical field-tested rule:When the site reports "the DCS reading is 0.5 mA lower than the local indicator", do not suspect the transmitter first. Use a signal source to inject 20 mA directly on the safe-area side of the barrier and check the acquisition card reading; if they match, the problem is on the field side of the barrier or in the wiring; if they do not match, the problem is in the barrier itself or the acquisition card. This sectional method is much faster than swapping meters one by one.

← Back to Knowledge Sharing

Online customer service
Online customer service Scan or click to contact directly
Contacts
Miss Chen(Safety barriers, isolators, surge protectors)
Ms Chen Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:2501529964

Phone:17717626508

Email:chenjing@qishan-sh.com

Miss Lu(Field Instruments, Valve Accessories, Terminal Blocks)
Ms Lu Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:1695457483

Phone:13636420802

Email:lhm@qishan-sh.com

Mr. Ye(Technical Support, After-Sales Service)

QQ:97010638

Phone:15800474322

Email:web@qishan-sh.com

Online Message

Please fill in the name

Please fill in a valid contact phone number (7-20 digits)

Please enter a valid email address

Please enter the requirement description (at least 10 characters)