A specific worked example ties the previous points together. The following values are for illustration only; actual projects must substitute the nameplate data of the selected products.
Given condition
| Item | Value | Source |
|---|---|---|
| Safety barrier Uo / Io / Po | 28 V / 93 mA / 0.65 W | Safety barrier nameplate (example) |
| Safety barrier Co / Lo | 83 nF / 4.0 mH | Table values corresponding to the above Uo/Io |
| Transmitter Ui / Ii / Pi | 30 V / 100 mA / 0.75 W | Transmitter nameplate (example) |
| Transmitter Ci / Li | 5 nF / 0 μH | Transmitter nameplate (example) |
| Cable capacitance / inductance | 150 pF/m / 1.0 μH/m | Cable datasheet (example) |
Step 1: Voltage, current and power matching
28 ≤ 30 ✓ 93 ≤ 100 ✓ 0.65 ≤ 0.75 ✓ All three pass.
Step 2: Maximum length limited by capacitance
Permitted cable capacitance = Co − Ci = 83 − 5 = 78 nF = 78,000 pF.
Maximum length = 78,000 ÷ 150 ≈ 520 m.
Step 3: Maximum length limited by inductance
Permitted cable inductance = Lo − Li = 4.0 − 0 = 4.0 mH = 4000 μH.
Maximum length = 4000 ÷ 1.0 = 4000 m.
Step 4: Take the smaller value and allow margin
Of the two limits, capacitance is the stricter, so take 520 m. Allowing a further 20% engineering margin, the practical permitted length is approximately 400 m.
How to read the conclusion:The bottleneck in this loop is capacitance, not inductance, and not voltage. To extend the distance, the most effective measure is to use low-capacitance cable (e.g. 90 pF/m raises the limit to approximately 860 m), rather than a higher-power barrier — the latter may actually reduce Co.
One more item to addVoltage drop verification: for a 400 m two-core loop, 1.0 mm² copper conductor resistance is about 18.5 Ω/km, so the 0.8 km round trip is about 14.8 Ω, giving a voltage drop of 0.30 V at 20 mA. Adding the barrier's internal resistance and terminal contact resistance, confirm the transmitter terminal voltage is still above its minimum operating voltage (typically 12 V); only then is this item complete.