How to Calculate Intrinsically Safe Circuit Cable Length: A Complete Worked Example

Intrinsically safe circuit design · 23 November 2026

A specific worked example ties the previous points together. The following values are for illustration only; actual projects must substitute the nameplate data of the selected products.

Given condition

Item Value Source
Safety barrier Uo / Io / Po 28 V / 93 mA / 0.65 W Safety barrier nameplate (example)
Safety barrier Co / Lo 83 nF / 4.0 mH Table values corresponding to the above Uo/Io
Transmitter Ui / Ii / Pi 30 V / 100 mA / 0.75 W Transmitter nameplate (example)
Transmitter Ci / Li 5 nF / 0 μH Transmitter nameplate (example)
Cable capacitance / inductance 150 pF/m / 1.0 μH/m Cable datasheet (example)

Step 1: Voltage, current and power matching

28 ≤ 30 ✓ 93 ≤ 100 ✓ 0.65 ≤ 0.75 ✓ All three pass.

Step 2: Maximum length limited by capacitance

Permitted cable capacitance = Co − Ci = 83 − 5 = 78 nF = 78,000 pF.

Maximum length = 78,000 ÷ 150 ≈ 520 m.

Step 3: Maximum length limited by inductance

Permitted cable inductance = Lo − Li = 4.0 − 0 = 4.0 mH = 4000 μH.

Maximum length = 4000 ÷ 1.0 = 4000 m.

Step 4: Take the smaller value and allow margin

Of the two limits, capacitance is the stricter, so take 520 m. Allowing a further 20% engineering margin, the practical permitted length is approximately 400 m.

How to read the conclusion:The bottleneck in this loop is capacitance, not inductance, and not voltage. To extend the distance, the most effective measure is to use low-capacitance cable (e.g. 90 pF/m raises the limit to approximately 860 m), rather than a higher-power barrier — the latter may actually reduce Co.

One more item to addVoltage drop verification: for a 400 m two-core loop, 1.0 mm² copper conductor resistance is about 18.5 Ω/km, so the 0.8 km round trip is about 14.8 Ω, giving a voltage drop of 0.30 V at 20 mA. Adding the barrier's internal resistance and terminal contact resistance, confirm the transmitter terminal voltage is still above its minimum operating voltage (typically 12 V); only then is this item complete.

← Back to Knowledge Sharing

Online customer service
Online customer service Scan or click to contact directly
Contacts
Miss Chen(Safety barriers, isolators, surge protectors)
Ms Chen Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:2501529964

Phone:17717626508

Email:chenjing@qishan-sh.com

Miss Lu(Field Instruments, Valve Accessories, Terminal Blocks)
Ms Lu Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:1695457483

Phone:13636420802

Email:lhm@qishan-sh.com

Mr. Ye(Technical Support, After-Sales Service)

QQ:97010638

Phone:15800474322

Email:web@qishan-sh.com

Online Message

Please fill in the name

Please fill in a valid contact phone number (7-20 digits)

Please enter a valid email address

Please enter the requirement description (at least 10 characters)