Insulation withstand voltage is the "isolation baseline" of an intrinsically safe system: between the intrinsically safe circuit and earth, and between the intrinsically safe circuit and non-intrinsically safe circuits, the specified test voltage must be withstood without breakdown.
| Location | Typical test voltage | Description |
|---|---|---|
| Intrinsically safe circuit to earth | ≥ 500 V AC | General requirement; determine specifically by equipment rated voltage and standards |
| Between intrinsically safe circuits and non-intrinsically safe circuits | ≥ 1500 V AC | Core specification of isolated safety barriers |
| Between isolated barrier input/output/power supply | 1.5 kV AC / 1 min (typical) | High-performance products can reach 2.5 kV |
During testing, note:Withstand voltage testing may damage some components, especially circuits with semiconductor protection. On site, withstand voltage tests are generally not performed arbitrarily; instead, insulation resistance is measured with an insulation resistance tester (e.g. 500 V megohmmeter), with reference to the test method specified by the manufacturer.
Re-inspection after maintenance:After replacing safety barriers, modifying wiring, or water ingress/moisture absorption, insulation resistance should be measured and recorded. A significant drop in insulation resistance (e.g. from >100 MΩ to a few MΩ) indicates moisture or insulation damage; in this case, even if functionality is normal, it should not be put into operation — insulation failure in intrinsically safe systems is gradual, and by the time breakdown occurs it is already too late.