Yes, but select anintrinsically safe or approved associated typesurge protective device, and it must be included in the intrinsic safety parameter calculation. Connecting an ordinary surge protective device to an intrinsically safe circuit will compromise both energy limitation and lightning protection.
Three configuration methods
- Safe-area side: Install a surge protective device on the safe-area side of the barrier; this does not affect the intrinsic safety parameters and is the most common practice;
- Hazardous-area side: An intrinsically safe surge protective device must be selected, and its
Ci / Liand residual voltage must both be included in the circuit calculation; - Integrated type: Some barriers have built-in surge protection; the manufacturer has already obtained overall certification, so simply confirm this during selection.
| Mounting position | Whether it affects the intrinsic safety parameters | Selection requirements |
|---|---|---|
| Safe-area side (after the barrier) | No effect | Standard industrial grade is sufficient |
| Hazardous-area side (before the barrier) | Affects Ci/Li and Uo | Must be intrinsically safe type, with parameters included in the calculation |
| Built-in type | Already calculated by the manufacturer | Verify certificate coverage |
Common mistake:Connecting a standard varistor-type surge protective device directly in parallel on the hazardous-area side. The junction capacitance of a varistor can reach several hundred pF to several nF, far exceeding the Co permitted by the safety barrier, and after ageing and short-circuiting it will alter the loop characteristics. This connection appears to add "an extra layer of protection" but actually introduces a new non-compliance point.