The following ten items come from high-frequency issues found in on-site inspections and can be used as a design self-check list.
- Matching only voltage and current without calculating capacitance and inductance: the most common omission in long-cable projects.
- Using Uo × Io instead of Po: this yields an excessively large power, leading to misjudgement of non-matching or failure to detect exceedances.
- Taking the maximum Co / Lo instead of looking up the table according to the actual Uo / Io: the safety margin is overestimated.
- Calculating cable inductance based on one-way length: inductance should be counted for the round trip, otherwise the stored energy is underestimated.
- Treating an integrated temperature transmitter as a simple apparatus: it contains electronic circuitry and must be certified.
- Zener barrier grounded in series or grounding conductor too thin: hidden risk of simultaneous multi-channel failure.
- Intrinsically safe and non-intrinsically safe circuits sharing a cable: hard to spot on drawings, but will certainly fail inspection.
- Installing ordinary surge protectors on the hazardous-area side: junction capacitance erodes the Co margin.
- Not recalculating after instrument replacement: the new model's Ci/Li may be larger.
- No retained calculation records: cannot prove compliance at acceptance and inspection.
Turn the checklist into a process:It is recommended to standardise an "Intrinsic Safety Loop Calculation Sheet" in the project, containing the five inequalities, cable parameters, calculation process, conclusion and signature. It serves three purposes at once: design verification, construction basis, and acceptance evidence. Spending an extra twenty minutes filling in the form upfront is more cost-effective than supplementing documentation afterwards.