The distributed parameters of a cable depend on its construction: conductor cross-section, shielding method, whether armoured, and whether twisted. Values should come from the cable manufacturer's product data; only use empirical estimates when these are genuinely unavailable.
| Cable type | Distributed capacitance (reference) | Distributed inductance (reference) |
|---|---|---|
| Standard shielded twisted pair (1.0 mm²) | Approx. 100–150 pF/m | Approx. 0.8–1.0 μH/m |
| Shielded multicore (1.5 mm²) | Approx. 150–200 pF/m | Approx. 0.7–0.9 μH/m |
| Armoured shielded cable | Approx. 180–250 pF/m | Approx. 0.9–1.2 μH/m |
| Low-capacitance dedicated intrinsically safe cable | Approx. 60–90 pF/m | Approx. 0.6–0.8 μH/m |
Note: The above are engineering reference ranges; values vary considerably between manufacturers. Formal calculations must be based on product datasheet data.
Three common pitfalls
- Whether length is based on "one-way" or "round-trip": For distributed capacitance, simply multiply the one-way length by the coefficient (capacitance is between the conductor and the shield and is independent of round-trip); for distributed inductance, calculating by the total loop length (round-trip) is more conservative. Use a consistent basis for calculations and note it in the records.
- Inter-core capacitance of multicore cables: If multiple intrinsically safe circuits share the same cable, the capacitance between cores will accumulate and must be calculated using the worst-case combination.
- Junction boxes and terminals: Intermediate junction boxes and terminal blocks introduce additional capacitance (albeit small), which should be included for long-distance multi-stage connections.
Design-stage approach:First look up pF/m for the cable type, then divide by the permissible length to derive the "maximum permissible length". Writing this figure into the construction drawings is more proactive than calculating after installation. For most projects, this is the bottleneck.