Digital output circuits often carry relays or solenoid valves; such loads areinductive loads, which generate induced overvoltage at the moment of power-off, imposing additional requirements on the energy-limiting design.
Three limits
- Coil current must not exceed Io: both the steady-state current and the pull-in surge of the solenoid valve coil must be within the Io of the safety barrier;
- Coil inductance must be included in Li: the solenoid valve coil itself is an inductance, and its value must be calculated together with the cable inductance, otherwise Lo will be exceeded;
- Freewheeling protection must be added: connect a freewheeling diode or RC snubber across the coil to suppress power-off overvoltage. Note, however—the freewheeling component must be on the intrinsically safe side, and its connection must not compromise the energy-limiting structure.
| Load | Typical inductance | Notes |
|---|---|---|
| Small signal relay | tens of mH | The inductance is relatively large and easily consumes the Lo margin |
| Intrinsically safe solenoid valve (low power) | A few mH to several tens of mH | Pick-up power and holding power must be verified |
| LED indicator | Negligible | Note the power dissipation of the series current-limiting resistor |
Recommended design sequence:First select the solenoid valve according to process requirements (bore, differential pressure, material), then use the coil parameters obtained to work backwards to determine the required Io of the safety barrier, and finally verify whether Lo is sufficient. Selecting the barrier first and then the valve often leads to the awkward situations of "valve fails to pick up" or "barrier cannot drive the load".