These are two different levels of concept in intrinsic safety certification, and they directly determine whether the user must perform their own calculations.
| Type | Content | User workload | Flexibility |
|---|---|---|---|
| Parameter certification(Ex certification) | Given for a single device only Uo/Io/Po/Co/Lo or Ui/Ii/Pi/Ci/Li |
The five inequalities must be calculated by the user | High; free combination possible |
| System certification | Certifies the combination of "safety barrier + specified field device model + specified cable conditions" | Can be adopted directly; no recalculation needed | Low; only certified combinations may be used |
The value of system certification lies ineliminates the user's calculation responsibility, but the trade-off is that the combination is locked: change to a different transmitter model and the system certificate becomes invalid. Parameter certification is flexible, but requires the user to have calculation capability and keep records.
Selection recommendations:For retrofit projects with few measurement points and uniform on-site device models, prioritise combinations with system certification — it is simpler and provides sufficient compliance evidence; for new-build projects with many measurement points, mixed models and possible future device replacement, parameter certification is more practical, but a calculation ledger must be established. Both approaches can be compliant; the key is to keep the evidence chain complete.