16 Channel HART Multiplexer Slave Module Type KFD0-HMS-16
16 channels, no external power supply required, HART field device input (protocol version 5–7), for use with HART multiplexer master module KFD2-HMM-16.
- Original Factory Genuine, Tenfold Compensation for Counterfeits
- Full Machine Warranty, Lifetime Maintenance
- In Stock, Shipped on the Same Day
Pepperl+Fuchs KFD0-HMS-16 HART multiplexer slave module, 16 channels, no external power supply required, HART field device input (protocol version 5–7), for use with HART multiplexer master module KFD2-HMM-16, up to SIL 3 (in accordance with IEC/EN 61508).
Part of the HART Interface Devices series, used for communication access, signal tapping and commissioning configuration between DCS/PLC control systems and HART field instruments, supporting HART protocol (including WirelessHART) multiplexing, loop conversion and filtering, and compatible with mainstream barriers and termination boards.
| Parameter Name | Technical Specifications |
|---|---|
| Functional safety parameters | |
| Safety Integrity Level (SIL) | SIL 3 |
| Power Supply | |
| Connection | via 14-channel flat cable of KFD2-HMM-16 master module |
| HART signal channel (non-intrinsically safe) | |
| Conformity | HART field device input (protocol version 5–7) |
| Connection | 26-pin flat cable for analog connections, 14-pin flat cable for primary module/secondary module connection between KFD2-HMM-16 and KFD0-HMS-16 |
| Leakage current | < 3 µA at −20 … 85 °C (−4 … 185 °F) |
| Terminating resistor | external 230 … 500 Ω standard (up to 1000 Ω possible) |
| Output voltage | ≥ 400 mV ss (with the above terminating resistor) |
| Output resistance | ≤100 Ω, capacitively coupled |
| Input Impedance | According to HART specification |
| Input voltage range | 0.08 … 4 V ss ; typical ± 5.2 V as local reference |
| Indication/setting | |
| Marking | Reserved marking area on the front |
| Directive conformity | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Conformity | |
| Degree of protection | IEC 60529:2001 |
| Ambient Conditions | |
| Ambient Temperature | −20 … 65 °C (−4 … 149 °F) |
| Mechanical parameters | |
| Degree of protection | IP20 |
| Weight | approx. 100 g |
| Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) (W x H x D), housing type B1 |
| Installation Method | Mounts on 35 mm DIN mounting rail in accordance with EN 60715:2001 |
| Hazardous area application data | |
| Certificate | PF 07 CERT 1143 X |
| Marking | II 3G Ex nA IIC T4 Gc |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013, EN 60079-15:2010 |
| General information | |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals and manuals within the applicable scope. For related information, see www.pepperl-fuchs.com. |
- 16-channel
- No external power supply required
- HART field device input (protocol version 5–7)
- For use with HART multiplexer master module KFD2-HMM-16
- Up to SIL 3 (in accordance with IEC/EN 61508)
Petrochemical Plant
HART field instrument commissioning and configuration communication
Power Energy System
DCS system HART multiplexer access
Process Automation
HART signal filtering and tapping between control room and field instruments
Need selection advice or bulk quotation?
Send us the working condition parameters (signal type, medium, range, pressure, temperature, connection method), and our engineers will provide a selection scheme and quotation within 1 working day.
- Phone consultation +86-21-66020232
- Email inquiry web@qishan-sh.com