Why zener safety barriers must be reliably earthed

Safety barriers and isolation technology · 23 November 2026

The voltage-limiting element of a zener safety barrier is the zener diode, which works as follows: when the line voltage exceeds the zener breakdown voltage it conducts, discharging the excess energy toearth. In other words,earth is its energy discharge path. Once earthing fails, the energy has nowhere to go after the zener diode conducts, the line voltage continues to rise, and the voltage-limiting function becomes ineffective.

Three mandatory earthing requirements

  • Earth resistance: the earth resistance of the dedicated earthing busbar for the intrinsically safe system is typically required to be no greater than 4 Ω (some standards and manufacturers require stricter values; designing to 1 Ω is more dependable), and equipotential bonding must be provided when it shares the same earthing grid with electrical protective earthing and lightning protection earthing.
  • Grounding conductor cross-section: The copper core cross-section of the main grounding conductor shall generally be no less than 16 mm², and branch conductors no less than 4 mm²; they shall be short, straight and thick, and shall avoid sharing a path with other high-current circuits.
  • Independent grounding point: The grounding terminal of the Zener barrier shall be connected to the dedicated intrinsically safe grounding busbar; it must not be regarded as grounded simply by being screwed to the cabinet frame or cable tray nearby.

The most typical failure scenarios on site:The grounding conductor was removed during cabinet modification and not restored; or a single thin wire is used to daisy-chain the grounding terminals of multiple barriers, forming a "daisy chain". The latter raises the ground potential of the entire chain of barriers in the event of a single-point fault, causing multiple channels to fail simultaneously. The correct practice is to run a separate conductor from each barrier's grounding terminal to the busbar.

Isolated barriers do not require this discharge path, because their energy limitation occurs on the isolated intrinsically safe side and is achieved independently by voltage- and current-limiting circuits, irrespective of the system ground potential. This is also the practical reason why isolated types are preferred where grounding conditions are poor.

Acceptance key points:Before commissioning, measure the resistance from the busbar to the grounding electrode with an earth resistance tester and keep a record; it must be re-measured after maintenance, and must not be judged by "it looks connected".

← Back to Knowledge Sharing

Online customer service
Online customer service Scan or click to contact directly
Contacts
Miss Chen(Safety barriers, isolators, surge protectors)
Ms Chen Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:2501529964

Phone:17717626508

Email:chenjing@qishan-sh.com

Miss Lu(Field Instruments, Valve Accessories, Terminal Blocks)
Ms Lu Personal WeChat QR Code

Scan WeChat QR code to add personal WeChat

QQ:1695457483

Phone:13636420802

Email:lhm@qishan-sh.com

Mr. Ye(Technical Support, After-Sales Service)

QQ:97010638

Phone:15800474322

Email:web@qishan-sh.com

Online Message

Please fill in the name

Please fill in a valid contact phone number (7-20 digits)

Please enter a valid email address

Please enter the requirement description (at least 10 characters)